Troubleshooting using the Error Log
Section 7-5
7-5-2
Error Codes
The error codes are described in the following table. The detailed error code
will provide detailed information on an error.
Note
1.
The time information from the CPU Unit is used in the PROFIBUS-DP
Master Unit.
2.
An error record is not created in non-volatile memory when the error con-
cerns an Error Log Write error.
Error
code
Meaning
Detailed error code
Correction
Non-
volatile
1st byte
2nd byte
0001
Watchdog timer error in CPU
Unit.
00
00
Replace the PLC CPU Unit.
Saved
0002
CPU Unit service monitor error.
Actual monitoring time ms (Hex)
Check the operating environment. Saved
000E
PLC Bus error.
00
00
Replace the CPU Unit.
Saved
0202
PROFIBUS parameter set
invalid.
00
80: Bus param-
eter error
00 ~ 7D: Slave
parameter error
• Check the parameter settings.
• re-download the configuration if
necessary.
---
020C
Protocol error
00
00 ~ 7D: Fail-
ing Master
Address
• Check the Master stations on
the network, and make sure they
are all working correctly.
• Check the HSA setting in CX-
Profibus, and make sure it is set
to the Master station with the
highest address on the network.
---
0211
Duplicate Master address
00
00 ~ 7D: Fail-
ing Master
Address
Check the Master Stations on the
network and ensure that they have
unique station addresses.
---
0219
Hardware error
00
00
• Check the network wiring, and
make sure it is correct.
• Check for short-circuits.
• Check the bus timing set
through CX-Profibus.
• Check if any other faulty devices
are on the same network.
• Verify that the Highest Station
Address setting includes any
other Master Address on the
bus.
---
0601
CPU Bus Unit fatal error.
Error address in program.
Restart the CPU Unit. If the prob-
lem persists, replace the PROFI-
BUS-DP Master Unit.
Saved
0602
CPU Bus Unit memory error.
01: Read error.
02: Write error.
02: Network
Parameter.
06: Error log.
Restart the CPU Unit. If the prob-
lem persists, replace the PROFI-
BUS Master Unit.
Saved
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...