153
Appendix
Slave Diagnostics Byte 2
A layout of Byte 2 is shown below. This byte is mapped to the low-byte of Word D.
05
Diag.Invalid_Slave_Response
This bit is set by the Master Unit if the slave has returned an invalid response to a
Master request message. The slave station will set this bit to 0.
06
Diag.Prm_Fault
Set by the slave station, this bit indicates that the last received parameter data
from the Master Unit have been rejected. The parameter data in the slave station
differ from the parameter sent by the Master Unit.
07
Diag.Master_Lock
This bit indicates that the slave station has been parameterized by another mas-
ter. The bit is set by the Master Unit, if the address in byte 4 differs from 255 and
from the Master Unit’s own address. The slave station sets this bit to zero.
Bit
Name
Description
00
Diag.Prm_Req
This bit is set by the slave station and indicates that it needs to be (re-)aparame-
terized. The slave station is not in Data_Exchange with the Master Unit. The bit
remains on as long as it has not been parameterized successfully.
01
Diag.Stat_Diag
This bit indicates static diagnostics at the slave station. The Master unit will
repeatedly request diagnostics data. As long as this bit is set, Data_Exchange
with the Master Unit is not being performed.
02
Reserved
This bit is reserved and always set to 1 by the slave station.
03
Diag.WD_On
If the watchdog has been enabled at the slave station (through the appropriate
setting in the parameterization message) this bit will be set.
04
Diag.Freeze_Mode
If the slave station has been set to the Freeze mode, using the global command,
this bit will be set to on. The bit will be set to off, if an Unfreeze command has
been received.
05
Diag.Sync_Mode
If the slave station has been set to the Sync mode, using the global command,
this bit will be set to on. The bit will be set to off, if an Unsync command has been
received.
06
Reserved
This bit is reserved.
07
Diag.Deactivated
This bit is set by the Master Unit, indicating that the slave station has been dis-
abled (i.e. using the STOP FINS command). The slave station is allocated to the
Master Unit, but removed from cyclic processing.
Bit
Name
Description
Byte 2
Diag.Deactivated
Diag.Sync_Mode
Diag.Freeze_Mode
Diag.WD_On
Diag.Stat_Diag
Diag.Prm_Req
7
6
5
4
3
2
1
0
Reserved
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...