46
IN
refresh
C200H PC
OUT
refresh
OUT
refresh
IN
refresh
Scan time
Instruction execution
Data for words
n through n+4
Data for word n+5
Voice Unit
OUT refresh (PC
→
Voice Unit)
IN refresh (Voice Unit
→
PC)
Number of playback repetitions
Repeat interval
Message output command
Stop command
ON-LINE flag
Message output in progress flag
Output message area FULL flag
Voice Unit error flag
Battery error flag
DIP switch setting status flags
Note The scan time increases to 3.5 ms when the Voice Unit is used in sentence
mode.
Flags and I/O Refresh Timing
•
ON-LINE flag (word n+5 bit 00)
The ON-LINE flag turns ON when input refreshing is executed after the
mode selector switch of the Voice Unit has been set to ON-LINE.
The ON-LINE flag turns OFF the next time input refreshing is executed af-
ter a switch from ON-LINE to any other mode has been made.
•
Message output in progress flag (word n+5 bit 02) (valid in ON-LINE mode
only)
This flag turns ON when input refreshing is executed during message play-
back. This flag turns OFF when the next input refreshing is executed, pro-
vided the message has been played back and the specified repeat interval
time has elapsed.
•
Output storage area and FULL flag (word n+5 bit 03) (valid in ON-LINE
mode only)
During one-shot operation a maximum of 20 messages excluding the mes-
sage in current playback can be stored in the output message area.
In sequential mode when all 20 messages are stored in this area, new ON
output commands are not accepted.
In priority mode, only the message having the lowest message number is
accepted while the message having the highest number is canceled.
The contents of the message area are sequentially incremented each time
a message has been played back.
ON-LINE Mode
Section 3-8