![background image](http://html.mh-extra.com/html/omron/sysmac-c200h-ov001/sysmac-c200h-ov001_operation-manual_1633422090.webp)
83
Errors in ERA mode
Display
Possible Cause
Correction
RUN
PLAY
REC
ERR
OVF
The memory protect switch is ON (in
this situation the error indication is
made when the mode selector switch is
operated or when the ST/SP switch is
pressed).
Turn OFF the memory protect switch
and press the ST/SP switch.
The RUN and ERR indicators are
lit. The PLAY and REC indicators
are blinking at 0.5 second intervals.
The LEDs display a message num-
ber.
RUN
PLAY
REC
ERR
OVF
(Blinking)
Error in message memory (1)
(The error indication is made when the
mode selector switch is operated). In
this case, data in the message memory
is for some reason defective.
In this situation the only solution is to
erase the entire memory. Press the
ST/SP switch to erase all the memory
contents.
The RUN indicator are lit.
The PLAY and REC indicators are
blinking at 0.5 second intervals.
The 7-segment LEDs display “00” at
0.5 second intervals.
RUN
PLAY
REC
ERR
OVF
One error
message is
displayed
blinking.
Error in message memory (2)
(Error results in one or two messages
because of a power failure that occurs
while messages are erased or
recorded.)
This error occurs when a power failure
occurs or when the PC is reset while
messages are erased or recorded.
In this situation the solution is to erase
the message responsible for the error.
Press the ST/SP switch to clear the
error code displayed on the LED
display.
The RUN indicator is lit.
The PLAY and REC indicators are
blinking at 0.5 second intervals.
The LEDs display one or alternately
two message numbers responsible
for the error.
RUN
PLAY
REC
ERR
OVF
(Blinking)
A message memory error (1) occurs
with the memory protect switch ON (in
this situation the error indication is
made when the mode selector switch is
operated or when the ST/SP switch is
pressed).
Turn OFF the memory protect switch
and press the ST/SP switch to erase
the entire contents of the message
memory.
The RUN and ERR indicators are
lit. The PLAY and REC indicators
are blinking at 0.5 second intervals.
The 7-segment LEDs display “00”
blinking at 0.5 second intervals.
Error Codes
Section 5-1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com