ERR LED Indicator
The Error LED (ERR) indicates the presence and type of an error within the Industrial Panel PC.
Color
Status
Meaning
Red
Not lit
•
The 24 VDC power is not supplied
•
No error is present
Blinking
•
Fan Error
•
Battery low
Lit
•
Thermal shutdown
•
Watchdog Error
•
Power Supply undervoltage error
•
Power Supply overvoltage error
•
Power supply defective
Additional Information
• The status of this LED can also be defined by users using the Industrial PC System API.
Refer to
3-3-2 Industrial PC System API
on page 3 - 25 for Industrial PC System API details.
• Refer to
on page 7 - 13 for actions to solve errors.
HDD LED Indicator
The Hard Disk Drive LED (HDD) indicates activity of the HDD or SSD.
Color
Status
Meaning
Yellow
Flickering
The HDD or SSD is active.
RUN LED Indicator
The RUN LED is available for user applications.
Color
Status
Meaning
Green
Not lit
User-defined.
The status can be defined in a user program using the
Industrial PC System API.
Blinking
Lit
Additional Information
Refer to
3-3-2 Industrial PC System API
on page 3 - 25 for Industrial PC System API details.
2 Hardware
2 - 6
NY-series Industrial Panel PC User's Manual (W555)
Summary of Contents for NYP17-*-11 SERIES
Page 32: ...Sections in this Manual 30 NY series Industrial Panel PC User s Manual W555 ...
Page 40: ...1 Overview 1 8 NY series Industrial Panel PC User s Manual W555 ...
Page 64: ...2 Hardware 2 24 NY series Industrial Panel PC User s Manual W555 ...
Page 182: ...5 Installation 5 62 NY series Industrial Panel PC User s Manual W555 ...
Page 236: ...7 Maintenance 7 46 NY series Industrial Panel PC User s Manual W555 ...
Page 258: ...Appendices A 22 NY series Industrial Panel PC User s Manual W555 ...
Page 259: ...I Index I 1 NY series Industrial Panel PC User s Manual W555 I ...
Page 262: ......
Page 263: ......