10
Simulate a power interruption and confirm a correct shutdown of the Panel PC.
• Start the Panel PC
• Start applications
• Create a power interruption
• Monitor the shutdown sequence and confirm a correct shutdown sequence
The UPS is connected and configured.
The Panel PC will shut down properly in case of a power supply interruption and restart automatically
when the power is restored.
Additional Information
The default
Input sensitivity setting
is
Standard voltage sensitivity
and this is correct.
Do not set this parameter to
Low voltage sensitivity
. Doing so can cause a system malfunc-
tion when switching to battery mode.
5 Installation
5 - 56
NY-series Industrial Panel PC User's Manual (W555)