5-3-3
Temperature
The temperature inside a control panel may be at least 10 to 15°C higher than outside the panel. Im-
plement the following measures against overheating at the installation site and in the control panel,
and allow a sufficient margin for the temperature.
Distance for Cooling
Adequate airflow around the Industrial Panel PC is required.
Additional Information
• The ambient temperature must be within the operating range.
Refer to
4-5-1 Operation Environment Specifications
on page 4 - 25 for temperature specifi-
cations.
• Allow space to accommodate for the bending radius of the cables.
Refer to
on page 2 - 21 for DVI cable bending requirements
and to
2-9-5 USB Type-A to USB Type-B Cables
on page 2 - 21 for USB cable bending re-
quirements.
Provide enough space for good air flow and ensure the following minimum distances are observed
around the sides of the Industrial Panel PC for landscape
A
and portrait
B
orientations.
A
B
B
+
A
X
X
X
X
Y
Y
Y
Y
Z
Item
X
50 mm
Y
100 mm
Z
50 mm
*1.
Measure the minimum distances X and Y at the air openings in the sides of the Industrial Panel PC.
5 Installation
5 - 16
NY-series Industrial Panel PC User's Manual (W555)
Summary of Contents for NYP17-*-11 SERIES
Page 32: ...Sections in this Manual 30 NY series Industrial Panel PC User s Manual W555 ...
Page 40: ...1 Overview 1 8 NY series Industrial Panel PC User s Manual W555 ...
Page 64: ...2 Hardware 2 24 NY series Industrial Panel PC User s Manual W555 ...
Page 182: ...5 Installation 5 62 NY series Industrial Panel PC User s Manual W555 ...
Page 236: ...7 Maintenance 7 46 NY series Industrial Panel PC User s Manual W555 ...
Page 258: ...Appendices A 22 NY series Industrial Panel PC User s Manual W555 ...
Page 259: ...I Index I 1 NY series Industrial Panel PC User s Manual W555 I ...
Page 262: ......
Page 263: ......