132
Inverter Specifications
Chapter 9-1
9-1
Inverter Specifications
3-phase
200-V AC
models
Model CIMR-J´7AZ
20P1
20P2
20P4
20P7
21P5
22P2
24P0
Power
supply
Rated voltage
and frequency
3-phase 200 to 230 V AC at 50/60 Hz
Allowable voltage
fluctuation
–15% to 10%
Allowable frequency
fluctuation
±5%
Power supply capacity (kVA)
(See note 1.)
0.4 0.9 1.6 2.7 4.3 5.9 9.3
Heat radiation (W)
13.0 18.0 28.1 45.1 72.8 94.8 149.1
Weight (kg)
0.5 0.5 0.8 0.9 1.3 1.5 2.1
Cooling method
Natural cooling
Cooling fan
Single-
phase
200-V AC
models
Model CIMR-J7AZ
B0P1
B0P2
B0P4
B0P7
B1P5
---
---
Power
supply
Rated voltage and
frequency
Single-phase 200 to 240 V AC at 50/60 Hz
Allowable voltage
fluctuation
–15% to 10%
Allowable frequency
fluctuation
±5%
Power supply capacity (kVA)
(See note 1.)
0.5 0.9 1.6 2.7 4.3 ---
---
Heat radiation (W)
(See note 2.)
14.1 20.0 31.9 51.4 82.8 ---
---
Weight (kg)
0.5 0.5 0.9 1.5 1.5 ---
---
Cooling method
Natural cooling
Cooling fan
Max. applicable motor capacity (kW)
0.1 0.2 0.4 0.75
1.5 2.2 3.7
Output
specifi-
cations
Rated output capacity (kVA)
0.3 0.6 1.1 1.9 3.0 4.2 6.7
Rated output current (A)
0.8 1.6 3.0 5.0 8.0 11.0
17.5
Rated output voltage (V)
3-phase 200 to 240 V AC (according to the input voltage)
Max. output frequency
400 Hz parameter setting
Control
charac-
teristics
Harmonic-current
countermeasures
DC reactor (option) connection possible
Control method
Sine wave PWM (V/f control)
Carrier frequency
2.5 to 10.0 kHz (in vector control)
Frequency control range
0.1 to 400 Hz
Frequency precision
(temperature characteristics)
Digital commands: ±0.01% (–10°C to 50°C)
Analog commands: ±0.5% (25°C ±10°C)
Frequency setting resolution
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
Output frequency resolution
0.01 Hz
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...