146
List of Parameters
Chapter 10
List of Parameters
Para-
meter No.
(Register
No. (Hex))
Name Description
Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page
n01
(0101)
Parameter
write-
prohibit
selection/
parameter
initialization
Used to prohibit parameters to be written,
sets parameters, or change the monitor
range of parameters.
Used to initialize parameters to default
values.
0: Sets or monitors parameter n01.
Parameters n02 through n79 can be
monitored only.
1: Sets or monitors parameters n01
through n79.
6: Clears the error log.
8: Initializes parameters to default
values in 2-wire sequence.
9: Initializes parameters to default
values in 3-wire sequence.
0, 1, 6,
8, 9
1 1 No 5-2
n02
(0102)
Operation
command
selection
Used to select the input method for the RUN
and STOP commands in remote mode.
0: The RUN and STOP/RESET Keys on
the Digital Operator are enabled.
1: Multi-function inputs through the
control circuit terminals in 2- or 3-wire
sequence.
2: Operation commands via RS-422A/
485 communications are enabled.
Note
The RUN command only through key
sequences on the Digital Operator is
acceptable in local mode.
0 to 2
1
0
No
5-7
n03
(0103)
Frequency
reference
selection
Used to set the input method for the
frequency reference in remote mode.
0: Digital Operator
1: Frequency reference 1 (n21)
2: Frequency reference control circuit
terminal (0 to 10 V)
3: Frequency reference control circuit
terminal (4 to 20 mA)
4: Frequency reference control circuit
terminal (0 to 20 mA)
6: Frequency reference via RS-422A/
485 communications
0 to 4,
6
1 0 No 5-8
n04
(0104)
Interrup-tion
mode
selection
Used to set the stopping method for use
when the STOP command is input.
0: Decelerates to stop in preset time.
1: Coasts to stop (with output shut off by
the STOP command)
0, 1
1
0
No
5-16
n05
(0105)
Reverse
rotation-
prohibit
selection
Used to select the operation with the reverse
command input.
0: Reverse enabled.
1: Reverse disabled.
0, 1
1
0
No
5-15
n06
(0106)
STOP/
RE-SET Key
function
selection
Used to select the stop method in remote
mode with n02 for operation mode selection
set to 1.
0: STOP/RESET Key of the Digital
Operator enabled.
1: STOP/RESET Key of the Digital
Operator disabled.
0, 1
1
0
No
5-7
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...