Wiring
Chapter 2-2
Grounding the Shield
In order to ground the shield securely, it is recommended that a cable clamp
be directly connected to the ground plate as shown below.
LVD Conformance
• Always connect the Inverter and power supply via a molded case circuit
breaker (MCCB) suitable to the Inverter for protecting the Inverter from
damage that may result from short-circuiting.
• Use one MCCB per Inverter.
• Select a suitable MCCB from the following table.
• With 400-V Inverters, it is necessary to ground to the power supply’s
neutral phase.
300V Models
Ground plate
Cable clamp
Cable
Shield
Inverter
MCCB (Mitsubishi Electric)
Model CIMR-J7AZ-
Type
Rated current (A)
20P1
NF30
5
20P2
5
20P4
5
20P7
10
21P5
20
22P2
20
24P0
30
B0P1
NF30
5
B0P2
5
B0P4
10
B0P7
20
B1P5
20