152
List of Parameters
Chapter 10
n40
(0128)
Multi-function
output
(MA/MB
and MC output
terminals)
Used to select the functions of multi-function
output terminals.
0 to 7,
10 to
17
1
1
No
5-20
Set
value
Function
Description
0
Fault output ON: Fault output
(with protective
function working)
1 Operation
in
progress
ON: Operation in
progress
2 Frequency
detection ´
ON: Frequency
detection (with
frequency reference
coinciding with output
frequency)
3
Idling
ON: Idling (at less
than min. output
frequency)
4 Frequency
detection 1
ON: Output frequency
P
frequency detection
level (n58)
5 Frequency
detection 2
ON: Output frequency
O
frequency detection
level (n58)
6 Overtorque
being
monitored
(NO-contact
output)
Output if any of the
following parameter
conditions is satisfied.
n59: Overtorque
detection function
selection
n60: Overtorque
detection level
n61: Overtorque
detection time
NO contact: ON
with overtorque being
detected
NC contact: OFF
with overtorque being
detected
7 Overture
being
monitored
(NC-contact
output)
8 Not
used ---
9
10 Alarm
output
ON:
Alarm
being
detected
(Nonfatal error being
detected)
11 Base
block
in progress
Base block in
progress (in operation
with output shut-off)
12
RUN mode
ON: Local mode (with
the Digital Operator)
13 Inverter
ready
ON: Inverter ready to
operate (with no fault
detected)
14
Fault retry
ON: Fault retry
15 UV
in
progress
ON: Undervoltage
being monitored
Para-
meter No.
(Register
No. (Hex))
Name Description
Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...