23
Wiring
Chapter 2-2
Ground Wiring
• Always use the ground terminal with the following ground resistance:
200-V Inverter: 100 W or less
400-V Inverter: separate ground,10 W or less
• Do not share the ground wire with other devices such as welding
machines or power tools.
• Always use a ground wire that complies with technical standards on
electrical equipment and minimize the length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance
between the ground electrode and the ground terminal is too long, the
potential on the ground terminal of the Inverter will become unstable.
• When using more than one Inverter, be careful not to loop the ground
wire.
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...