59
Setting the Frequency Reference
Chapter 5-5
Setting the Frequency Reference with the FREF Indicator Lit
The frequency reference can be set while the FREF indicator of the Digital
Operator is lit in the following cases.
• Parameter n03 for frequency reference selection is set to 1, which
enables frequency reference 1, and the Inverter is in remote mode.
• Parameter n07 for frequency selection in local mode is set to 1, which
enables key sequences on the Digital Operator, and the Inverter is in local
mode.
• Frequency references 2 through 8 are set with multi-step speed reference
input.
The frequency reference can be changed, even during operation.
When the frequency reference is changed while the FREF indicator is lit, the
corresponding parameter is changed simultaneously. For example, if
frequency reference 2 has been selected with multi-function input (a multi-
step speed reference), the set value in n22 (for frequency reference 2) will be
changed simultaneously when the frequency reference is changed while the
FREF indicator is lit.
Take the following default steps, for example, to change the frequency
reference with the FREF indicator lit.
Setting the Key Sequential
Frequency (n08)
• The Enter Key need not be pressed when changing the setting in n08. In
that case, the frequency reference will change when the set value is
changed with the Increment or Decrement Key while the data display is
continuously lit.
Set Values
Key
sequence
Indicator Display
example
Explanation
Power On
Note
If the FREF indicator has not been lit, press the Mode Key
repeatedly until the FREF indicator is lit.
Use the Increment or Decrement Key to set the frequency reference.
The data display will flash while the frequency reference is set.
Press the Enter Key so that the set value will be entered and the data
display will be lit.
n08
Key Sequential Frequency Setting
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Value
Description
0
Enter Key enabled (The set value is entered with the Enter Key pressed.)
1
Enter Key disabled (The set value set is entered immediately.)
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...