87
Other Functions
Chapter 6-7
• When the RUN command for forward or reverse rotation is input, the
Inverter will start operating at the lower limit regardless of whether the UP/
DOWN command is input or not.
• When the UP/DOWN function and inching frequency command are both
assigned to multi-function inputs, an inching frequency command input
will have the highest priority.
• If n62 for UP/DOWN command frequency memory is set to 1, the output
frequency held by the UP/DOWN function for 5 s or more will be stored in
the memory. The output frequency will be held by the UP/DOWN function
when both UP and DOWN commands are ON or OFF together.
6-7-8
Error History (n78)
• The J7AZ stores information on the latest error.
• The information on the latest error recorded is displayed by pressing the
Enter Key after n78 for error history is displayed.
• The details of the information are the same as that obtained from the
multi-function monitor U09.
Note
The information is read only.
Display Example
To clear the error history, set n01 for parameter write-prohibit selection/
parameter initialization to 6.
n78
Error History
Changes during
operation
---
Setting
range
---
Unit of
setting
---
Default setting
---
Fault code
uU 1
· Fault display
· No error stored
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...