112
Register Number Allocations in Detail
Chapter 7-7
Broadcast Message with Slave Address: 00 (00 Hex) Write
Note
1.
Data can be written to registers 0001 and 0002 only. Assumed previous
values are held for unused registers.
2.
No data can be written to multi-function input.
3.
The unit of setting of the broadcast message is different from that in the
DSR message to communicate with a single Slave.
RUN Command (Register 0001 Hex)
7-7-2
Monitor Functions
Register No. (Hex)
Function
Description
0000 Not
used.
---
0001
RUN command
Refer to the table below.
0002
Frequency reference
Set the frequency reference based on the maximum
frequency as 30,000.
0003 to 000F
Not used.
---
Bit No.
Function
0
RUN command (1: RUN)
1 Forward/Reverse
(1:
Reverse)
2 to 3
Not used.
4
External fault (1: External fault EF0)
5
Fault reset (1: Fault reset)
4 to 15
Not used.
Register No. (Hex)
Function
Description
0020
Status signal
Refer to the following corresponding table.
0021
Fault status
Refer to the following corresponding table.
0022
Data link status
Refer to the following corresponding table.
0023
Frequency reference
According to the set value in n69.
0024
Output frequency
According to the set value in n69.
0025 to 0026
Not used.
---
0027
Output current
Read based on 1 A as 10.
0028
Output voltage
Read based on 1 V as 1.
0029 to 002A
Not used.
---
002B
Input terminal status
Refer to the following corresponding table.
002C
Inverter status 1
Refer to the following corresponding table.
002D
Output terminal status
Refer to the following corresponding table.
002E to 0030
Not used.
---
0031
Main circuit DC voltage
Read based on 1 V as 1.
0032 to 003C
Not used.
---
003D
Communications error
Refer to the following corresponding table.
003E to 00FF
Not used.
---
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...