DSR Message and Response
Chapter 7-4
Response
Normal
Error
Note
When an error occurs, the MSB of the function code will be set to 1.
Example of Data Read
In the following example, four-register data (status signal data) is read from
register 0020 Hex of the Inverter with a Slave address of 02.
DSR Message
Byte No.
Data
1 Slave
address
2
Function code (03 Hex)
3
Number of bytes of attached data
4
Data of start register
MS B
5
LSB
6
Data of next register
MSB
7
LSB
8
Data of next register
MSB
9
LSB
: :
:
n–1 CRC-16
check
n
Byte No.
Data
1 Slave
address
2
Function code (83 Hex)
3 Error
code
4 CRC-16
check
5
Byte No.
Data
Data example
(Hex)
1 Slave
address
02
2 Function
code
03
3
Register No. of read start data
00
4
20
5
Number of registers of read data
00
6
04
7 CRC-16
check
45
8
F0