Register Number Allocations in Detail
Chapter 7-7
Status Signal (Register 0020 Hex)
Fault Status (Register 0021 Hex)
Note
When a fault results, the corresponding bit will be set to 1.
Data Link Status (Register 0022 Hex)
Input Terminal Status (Register 002B Hex)
Bit No.
Function
0
During RUN (1: During RUN)
1
Forward/reverse operation (1: Reverse operation)
2
Inverter ready (1: Ready)
3 Fault
(1:
Fault)
4
Data setting error (1: Error)
5
Multi-function output (1: ON)
6 to 15
Not used.
Bit No.
Function
Bit No.
Function
0 OC
8 F
_
1 OV
9 OL1
2 OL2
10
OL3
3 OH
11
Not
used.
4 Not
used.
12
UV1
5 Not
used.
13
GF
6 Not
used.
14
CE
7 EF
_
, STP
15
Not used.
Bit No.
Function
0
Data writing (1: Writing)
1 to 2
Not used.
3
Upper and lower limit error (1: Error): Outside set range
4
Verify error (1: Error): Same as OPE
_
.
5 to 15
Not used.
Bit No.
Function
0
Forward/stop terminal (S1) (1: ON)
1
Multi-function input terminal 1 (S2) (1: ON)
2
Multi-function input terminal 2 (S3) (1: ON)
3
Multi-function input terminal 3 (S1) (4: ON)
4
Multi-function input terminal 4 (S5) (1: ON)
5 to 15
Not used.
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...