Vision System FH/FZ5 Series
User’s Manual (Z340)
FAQ
During Start-up
POWER LCD is not lit
• Is the power supply connected correctly?
• Is the supply voltage low (24 V DC +10%, -15%)?
Nothing is displayed on the monitor
• Is the monitor ON?
• Is the monitor cable connected correctly?
• Has the monitor failed?
• Is the power capacity enough (LCD monitor)?
• Have you turned off the LCD? If you have, the monitor recovery will occur if you tap on the
bottom of the monitor.
FH/FZ5 RUN and ADJUST windows are not displayed.
Camera connection:
• When the camera connection is checked and initialized during start-up, the system will not start unless
there is a response from the camera side. Check if the system starts with the camera cable disconnected.
Data corruption:
• The scene group data and system data saved to the controller have been corrupted.
In some cases when the power is shut down or the USB memory was removed while accessing the CF card in the controller,
such as when data is being saved to the controller, a scene group is being switched and a scene group is being saved to or
loaded from the USB memory, the data file may get corrupted. The file needs to be repaired. Please contact OMRON.
• Monitor images are disordered
• Are the power supply and cable generating electronic noise?
• Is the monitor cable connected correctly?
Input cannot be made
• Are the cables for input devices (mouse, etc) connected correctly?
• Is the angle too big when tapping is done with the touch pen?
Camera image does not display/Image is blurry
• Is the lens cap removed?
• Is the camera cable connected correctly?
• Is the lens aperture the maximum or the minimum?
• Is the camera's shutter speed correct?
• Is the lighting method correct?
Start-up is slow
• Was the system connected to a LAN when started?
If the system is started while connected to a LAN, startup may take a longer time.
During Operation
Measurement results do not display on the monitor
• Are windows other than the Main screen (the Edit Flow window, etc.) displayed?
• Are any setting windows open?
* A setting window is defined as a window that opens separately such as the Edit Flow window and the
Scene Maintenance window.
Summary of Contents for fh-1 series
Page 8: ...WWW NNC IR 6 Vision System FH FZ5 Series User s Manual Z340...
Page 14: ...WWW NNC IR 12 Vision System FH FZ5 Series User s Manual Z340 MEMO...
Page 22: ...WWW NNC IR 20 Vision System FH FZ5 Series User s Manual Z340 MEMO...
Page 48: ...WWW NNC IR Initializing the Controller 46 Vision System FH FZ5 Series User s Manual Z340 MEMO...
Page 68: ...WWW NNC IR Editing Scene Groups 66 Vision System FH FZ5 Series User s Manual Z340 MEMO...
Page 881: ...WWW NNC IR...