84
Setting Alarm Specifications
Section 5-4
(4) Set value: 5, Upper and lower-limit with standby sequence
Note
For the above upper and lower-limit alarm:
• In cases 1 and 2 above, the alarm is always OFF if the hystere-
sis overlaps the upper and lower limits.
• In case 3, the alarm is always OFF.
(5) Set value: 5, Upper and lower-limit with standby sequence
• The alarm is always OFF when the hysteresis overlaps the up-
per and lower limits.
5-4-2
Alarm Value
Alarm values are indicated by “X” in the table on the previous page. When the
upper and lower limits are set independently, “H” is displayed for upper limit
values, and “L” is displayed for lower limit values.
Note
(1) Refer to 5-7-1 Bank Function for details on banks.
(2) The decimal point position is the same as set for the Decimal Point Posi-
tion B parameter.
5-4-3
Alarm Hysteresis
• The hysteresis of alarm outputs when alarms are switched ON/OFF can
be set as follows:
• Alarm hysteresis can be set separately for each alarm.
Note
This parameter can be set only when operation is stopped.
The decimal point position is determined by the sensor selection. With analog
Variable
type
Parameter name
Setting range
Default
D0/90
Alarm Value 1 to 3
(Bank)
−
1999 to 9999 EU
(See note 2.)
0
Conditions for use The alarm type must not be set to an upper and lower limit
alarm.
Variable type
Parameter name
Setting range
Default
D0/90
Alarm Upper Limit Value 1 to 3
(Bank)
−
1999 to 9999 EU
(See note 2.)
0
Alarm Lower Limit Value 1 to 3
(Bank)
−
1999 to 9999 EU
(See note 2.)
0
Conditions for use The alarm type must be set to an upper and lower limit alarm,
upper and lower limit range alarm, or upper and lower limit
alarm with standby sequence.
Variable type
Parameter name
Setting range Default
E3/A3
Alarm 1 to 3 Hysteresis
(Channel) 0.1 to 999.9
EU
0.2
Conditions for use
The alarm type must not be set to 0.
Alarm Hysteresis
Alarm value
Upper-limit alarm
OFF
ON
Alarm value
Lower-limit alarm
OFF
ON
Alarm Hysteresis
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......