75
Setting Control Specifications
Section 5-3
■
MV at Stop
This parameter sets the MV when control is stopped.
For heating/cooling control, the MV at Stop parameter applies to the cooling
side if the MV is negative and to the heating side if the MV is positive.
The default is 0.0, so an MV will not be output for either standard or heating/
cooling control with the default setting.
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
■
MV at PV Error
This parameter sets the MV when an input error or remote SP input error
occurs.
The order of priority is as follows: Manual MV > MV at Stop > MV at PV
Error.
■
MV Limiter
This function limits the MV output by applying upper and lower limits to the
calculated MV.
• The following MVs take priority over the MV limits.
• Manual MV
• MV at Stop
• MV at PV Error
Time
MV
MV
changes
Power
OFF
Power
ON
MV
changes
Power
interrupted
Manual
Auto
Inherits the MV that existed
before the mode change.
Variable type
Parameter name
Setting range
Default
D5/95
MV at Stop (Channel)
−
5.0 to 105.0%
0
Conditions for use
No special conditions.
Variable type Parameter name
Setting range
Default
D5/95
MV at PV Error
(Channel)
−
5.0 to 105.0%
0
Conditions for use
No special conditions.
Output
100%
MV Lower Limit
MV Upper Limit
0%
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......