19
Wiring Terminals
Section 2-2
Wiring Procedure for
Screw-Less Clamp
Terminals
There are two holes for each terminal. The hole on the right is the operating
hole; the hole on the left is the wire hole.
Insert a flat-blade screwdriver with a width of 2.5 mm into the operating hole
and then insert the wiring into the wire hole.
The wire will be clamped when the screwdriver is removed.
Use crimp terminals for wiring that match the cross-sectional area of the
wiring material.
We recommend the following crimp terminals:
Weidmuller H-sleeve Series
2-2-3
Wiring
Power Supply Voltage
Connect the power supply to EDU terminals 8 and 9 as shown below.
• If reinforced insulation is required, connect the input and output terminals
to a device without any exposed current-carrying parts or to a device with
standard insulation suitable for the maximum operating voltage of the
power supply I/O section.
• Conforming to Safety Standards
The power supply terminals must be supplied from a SELV, limited-current
source. A SELV (separated extra-low voltage) source is a power supply
having double or reinforced insulation between the primary and the sec-
ondary circuits and having an output voltage of 30 V r.m.s. max. and 42.4
V peak max. or 60 VDC max.
Recommended power supply: S8VM Series or S8VS Series (both manu-
factured by OMRON)
Note
Select a power supply that suits the operating environment.
• To comply with the standards for noise terminal voltage for class A in EN
61326, install a noise filter (Densei Lambda MXB-1206-33 or the equiva-
lent) to the DC line as close as possible to the EJ1G.
B2
B3
B4
B5
B6
B7
B8
B1
A1
A2
A3
A4
A5
A6
A7
A8
B9
B10
A9
A10
8
9
1
2
3
4
5
6
7
8
9
EDU
24-VDC
input power
supply
+
−
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......