122
Other HFU Functions
Section 5-7
5-7-2
Event Inputs (TC2)
Event Input
Assignment
There are two event inputs in the TC2.
The following diagram shows the parameters that can be set in event input 1
or event input 2.
Some of the parameters are for all channels and others are for individual
channels.
Note
This parameter can be set only when operation is stopped.
When this parameter has been changed, the new setting becomes effective
the next time a software reset is performed for the Unit or the next time power
is turned ON.
Controlling Operation with
the Event Input’s ON/OFF
Status
• Operation can be switched by OFF-to-ON or ON-to-OFF event-input tran-
sitions.
■
Stop (0)/Run (1), Run (0)/Stop (1), Auto (0)/Manual (1)
Variable type
Parameter name
Setting range
Default
F2/B2
Event Input 1 to 4 Assignment
(Common)
0 to 69
0
Conditions for use
No special conditions.
Channel 64
Disabled
Stop (0)/Run (1)
Bank (bit 1)
Auto (0)/Manual (1)
Bank (bit 0)
All channels
Run (0)/Stop (1)
Channel 3
Channel 2
Stop (0)/Run (1)
Bank (bit 1)
Auto (0)/Manual (1)
Run (0)/Stop (1)
Channel 1
Bank (bit 0)
EV2 to EV4 can be set in the same way.
EV2
Settable
parameters
EV1
EV3
EV4
ON
OFF
Parameter
Event input
Description
Stop (0)/Run (1)
OFF
Stop
ON
Run
Run (0)/Stop (1)
OFF
Run
ON
Stop
Auto (0)/Manual (1)
OFF
Auto
ON
Manual
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......