51
Setting Input Specifications
Section 4-1
4-1-2
Temperature Inputs
■
Temperature Unit
Either °C or °F can be selected.
■
Cold Junction Compensation Method
Specifies whether cold-junction compensation is performed in the Tempera-
ture Controller or externally.
Enable external cold-junction compensation when using two thermocouples
to measure a temperature difference or using a external cold-junction com-
pensator for even greater precision.
4-1-3
Analog Inputs
When an analog input is selected, scaling can be performed as needed by the
control application.
• The Scaling Upper Limit, Scaling Lower Limit, and Decimal Point Position
parameters are used for scaling. These parameters cannot be used when
a temperature input type is selected.
• The Scaling Upper Limit parameter sets the physical quantity to be
expressed by the upper limit value of input, and the Scaling Lower Limit
parameter sets the physical quantity to be expressed by the lower-limit
value of input. The Decimal Point Position parameter specifies the num-
ber of digits below the decimal point.
• The following example shows scaling of an analog input (4 to 20 mA).
After scaling, the humidity can be read directly. In this case, the decimal
point is set for 1 digit below the decimal point.
Variable type
Parameter name
Setting range
Default
E0/A0
Temperature Unit
(Channel) 0: °C/1: °F
0
Conditions for use The input type must be set to temperature input.
Variable type
Parameter name
Setting range
Default
E0/A0
Cold Junction Compensation
Method (Common)
0: External /
1: Internal
1
Conditions for use
The input type must be set to thermocouple or infrared temperature sensor.
20
4
Input (mA)
Display
(humidity)
Upper limit (95.0%)
Lower limit (10.0%)
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......