Determining the Error from the Current Situation for Communications Errors
Section 7-4
G3ZA
Use the following table when the EJ1G cannot communicate with an G3ZA
connected to it.
Status
Possible cause
Countermeasure
Communications are
not possible between
the G3ZA and EJ1G
(the COM3 indicator
does not flash).
Power is not supplied to the
G3ZA.
Supply power to the G3ZA
from the power supply termi-
nals and reset the EJ1G.
The G3ZA is not connected to
the EJ1G.
Connect the G3ZA to the
EJ1G using an EJ1C-
CBLA050 Connecting Cable.
Pin 7 on SW2 on the EJ1G is
not ON.
Turn ON pin 7 on SW2 on the
EJ1G.
Power was not supplied to the
G3ZA when the EJ1G was
started.
Supply power to the G3ZA
and EJ1G at the same time or
to the G3ZA first.
Different baud rates are set in
the G3ZA and EJ1G.
Set SW2 on the G3ZA to 3
and reset the EJ1G.
The unit configuration was
registered when the G3ZA
was not connected to the
EJ1G (default condition).
Send the Resister Unit Con-
figuration: Reset operation
command to the EJ1G Basic
Unit to which the G3ZA is con-
nected to clear the Unit con-
figuration. The settings will be
valid after the EJ1G is reset.
The same unit number is set
for more than one G3ZA.
Set the G3ZA unit numbers so
that the same number is not
used more than once for the
same EJ1G Basic Unit.
The registered G3ZA Unit
configuration is different from
the connected G3ZA Unit con-
figuration.
Send the Resister Unit Con-
figuration: Reset operation
command to the EJ1G Basic
Unit to which the G3ZA is con-
nected to clear the Unit con-
figuration, and then reset the
EJ1G. When the EJ1G starts
again, send the Register Unit
Configuration: Register opera-
tion command to register the
connected G3ZA Units in the
configuration.
Note Bit 12 of variable type
C4/84 0013 in Device B
Status can be used to
see if the connected
G3ZA Unit configura-
tion has been regis-
tered.
The cable connecting the
G3ZA and EJ1G is broken.
Replace the Connecting
Cable between the G3ZA and
EJ1G.
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......