121
Other HFU Functions
Section 5-7
5-7
Other HFU Functions
5-7-1
Bank Function
Up to 4 banks can be created with the following parameters registered inde-
pendently.
The currently selected bank's parameters can be read or written by reading or
writing the “Present Bank” parameters.
The following table shows the relationship between the banks and variable
types.
Changing the Bank
The bank can be switched with an event input, internal bus, or operation com-
mand.
Changing the Bank With
an Event Input
The bank can be switched by setting Bank (Bit 0) in the Event Input 1 Assign-
ment and Bank (Bit 1) in the Event Input 2 Assignment, as shown in the fol-
lowing table.
Note
Event input 1 can be used alone to switch between banks 0 and 1.
Operation Commands
For details, refer to 6-4-11 Operation Commands.
■
Bank Number
The presently selected bank number can be checked with the following
parameter.
• Set Point
• Proportional Band
• Integral Time
• Derivative Time
• SP Ramp Rise Value • SP Ramp Fall Value • Alarm Value 1 to 3
• Alarm Upper Limit Value 1 to 3
• Alarm Lower Limit Value 1 to 3
Alarm Lower Limit Value 1 to 3
Proportional Band
Set point
Present bank
Alarm Lower Limit Value 1 to 3
Proportional Band
Set point
Present bank
Alarm Lower Limit Value 1 to 3
Proportional Band
Set point
Bank 1
Alarm Lower Limit Value 1 to 3
Proportional Band
Set point
Bank 2
Alarm Lower Limit Value 1 to 3
Proportional Band
Set point
Bank 3
Currently selected bank
Variable type
Bank
D0/90
Bank 0
D1/91
Bank 1
D2/92
Bank 2
D3/93
Bank 3
D4/94
Present Bank
Event input 2
Event input 1
Selected bank
OFF
OFF
Bank 0
OFF
ON
Bank 1
ON
OFF
Bank 2
ON
ON
Bank 3
Variable type
Parameter name
Setting range Default
C4/84
Bank No. Monitor
(Channel) 0 to 3
---
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......