132
Detailed Description of Services
Section 6-4
6-4
Detailed Description of Services
6-4-1
Read from Variable Area
This service reads from a variable area.
■
Command
Service Request PDU
■
Response
Service Response PDU
1.
Variable Type and Read Start Address
Refer to Parameter List on page 175.
2.
Bit Position
The EJ1G does not support bit access. Fixed to 00.
3.
No. of Elements
Note
The following values apply for the DA/9A variable types.
4.
Response Codes
5.
Precautions
• “0” is set when an address with no data set is read.
• If the start a number of elements exceeds FFFF, the address
returns to 0000.
MRC
2
2
0
1
4
SRC
2
0
1
2
0
0
4
Variable
type
Read start
address
Bit
position
No. of elements
Read data length
No. of elements
For double-word (8-digit) variable type
40 max. (0028H)
For word (4-digit) variable type
80 max. (0050H)
Read data length
No. of elements
For double-word (8-digit) variable type
25 max. (0019H)
For word (4-digit) variable type
50 max. (0032H)
Response code
Error name
Cause
1001
Command too long
The command is too long.
1002
Command too short
The command is not long enough.
1101
Area type error
The corresponding variable type does
not exist.
110B
Response too long
The number of elements exceeds the
maximum.
1100
Parameter error
Bit position is not 00.
7011
Operation error (7011) The command cannot be executed due
to a device error.
0000
Normal completion
Processing was completed normally.
MRC
2
0
1
4
SRC
2
0
1
Response
code
Read data
(for No. of elements)
No. of elements
×
8 or 4
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......