118
Programless Communications
Section 5-6
Details of Operation
Command Codes for
Programless
Communications
Note
(1) 000000: Backup 000001: RAM
(2) 000000: CH1 000001: CH2 ··· 111111: CH64
(3) 000000: Reset 000001: Register
(4) 0: For channels specified in the related information 1: All channels
Example: Operation Command Code to execute Run for channel 1 of
Unit No. 1
Not used.
All Units specified
Command code
Unit specification
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Write Mode
0
0
0
1
0
0
(See note 1.)
0
0
0
0
Software Reset
0
0
0
1
1
0
0
0
0
0
0
0
0
Run
0
0
1
0
1
0
(See note 2.)
(See
note
4.)
Stop
0
0
1
0
1
1
Manual
0
0
1
1
0
0
Auto
0
0
1
1
0
1
40% AT Execute
0
0
1
1
1
0
100% AT Execute
0
0
1
1
1
1
AT Cancel
0
1
0
0
0
0
GT Execute
0
1
0
0
0
1
GT Cancel
0
1
0
0
1
0
Bank 0 Change
0
1
1
1
1
0
Bank 1 Change
0
1
1
1
1
1
Bank 2 Change
1
0
0
0
0
0
Bank 3 Change
1
0
0
0
0
1
Reset Error
1
0
1
1
0
1
0
0
0
0
0
0
0
Alarm 1 Latch Cancel
1
1
0
0
1
0
(See note 2.)
(Se
e
not
e
4.)
Alarm 2 Latch Cancel
1
1
0
0
1
1
Alarm 3 Latch Cancel
1
1
0
1
0
0
All Alarm Latch Cancel
1
1
0
1
0
1
Save RAM Data
1
1
0
1
1
1
0
0
0
0
0
0
1
Register Unit Configuration
1
1
1
0
1
1
(See note 3.)
0
Command code for Run
Unit specification: 01
Channel 1
0
0
1
0
1
0
0
0
0
0
0
1
0
0
0
0
H’ 2
H’8
H’ 1
H’ 0
H’ 2810
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......