82
Setting Control Specifications
Section 5-3
• If an input error occurs at channel 6 while the Operation During Error
(Selection C) parameter is set to 2 (control stopped):
Group 2 will change to STOP mode (control stopped).
• If a zero-cross error has occurred at the G3ZA while the Operation During
Error (Selection C) parameter is set to 2 (control stopped):
Group 2 will change to STOP mode (control stopped).
A zero-cross error will occur for all channels at Communications Unit No.
6 connected to the G3ZA and channels 14 and 15 will change to STOP
mode (control stopped).
• If a HB alarm occurs at channel 13 while the Operation During Error
(Selection D) parameter is set to 0 (Notification only (Continue)).
Channel 13 will continue control. The HB alarm status for channel 13 can
be checked at bit 11 (Basic Unit Alarm) of Channel Alarm Status - CH13
for variable type C4/84, address 0D02.