Setting Output Specifications
Section 4-2
4-2
Setting Output Specifications
4-2-1
Control Output Method
The time-proportional output method is used for the control output.
The MV determines the percentage of time that the output is ON during each
control period.
Note
Control responsiveness improves as the control period is short-
ened, but if relays are being used for heater control, the relay life-
time will also be shortened so we recommend using a control
period of at least 20 seconds.
Note
If the parameter is set to 0, the period will be 0.5 s.
4-2-2
Alarm Outputs (TC2 Units Only)
Output 3 and output 4 from TC2 Units are used to output alarm 1 for the
channel assigned to the TC2 Unit.
Example for the Following Groups
• If alarm 1 for channel 6 turns ON, output 3 from the TC2 Unit with com-
munications unit number 3 turns ON.
• If alarm 1 for channel 10 turns ON, output 4 from the TC2 Unit with com-
munications unit number 4 turns ON.
Variable type
Parameter name
Setting range
Default
E1/A1
Control Period 1 to 4
(I/O) 0 to 99 s
2
Conditions for use
No special conditions.
ON
100%
80%
60%
40%
20%
Control
period
OFF
H
F
U
E
D
U
0 1 2
3
4
5
6
TC2
CH1
CH2
TC2 TC2 TC2 TC2 TC2
CH3 CH6 CH9 CH11 CH14
CH5 CH7 CH10 CH13 CH15
Group 1 (gradient)
Group 2 (gradient)
Group 3 (gradient)
Group 4 (2-PID control)
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......