187
Parameter List
Appendix
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
F1 (B1)
Enabled
after
resetting.
0000
Number of Enabled Groups
H' 00000001 to H' 00000010 (1 to 16)
1
---
Common
---
●
0100
Starting Communications Unit Number
H' 00000000 to H' 0000001F (0 to 31)
1
---
GRP
---
●
0101
Starting Channel
H' 00000000 to H' 00000003 (0 to 3)
0
---
GRP
---
●
0102
Number of Enabled Channels
H' 00000002 to H' 00000020 (2 to 32)
2
---
GRP
---
●
0103
Control Type
H' 00000000: Gradient temperature control (0)
H' 00000001: 2-PID control (1)
0
---
GRP
---
●
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
F2 (B2)
Enabled
after
resetting.
0000
Event Input 1 Assignment
H' 00000000: Disabled (0)
H' 00000001: All channels Bank (bit0) (1)
H' 00000002: All channels Bank (bit1) (2)
H' 00000003: All channels Stop (0)/Run (1) (3)
H' 00000004: All channels Run (0)/Stop (1) (4)
H' 00000005: All channels Auto (0)/Manual (1) (5)
0
---
Common
---
●
Not used.
H' 00000020: CH1 Bank (bit0) (32)
H' 00000021: CH1 Bank (bit1) (33)
H' 00000022: CH1 Stop (0)/Run (1) (34)
H' 00000023: CH1 Run (0)/Stop (1) (35)
H' 00000024: CH1 Auto (0)/Manual (1) (36)
Not used.
H' 00000040: CH2 Bank (bit0) (64)
The rest are the same as channel 1.
H' 00000800: CH64 Bank (bit0) (2048)
The rest are the same as channel 1.
0001
Event Input 2 Assignment
The rest are the same as Event Input 1 Assignment.
0002
Event Input 3 Assignment
The rest are the same as Event Input 1 Assignment.
0003
Event Input 4 Assignment
The rest are the same as Event Input 1 Assignment.
Not used.
0010
Auxiliary Output 1 Assignment
H' 00000000: Disabled (0)
H' 00000001: Temperature Controller error (1)
4
---
Common
---
●
H' 00000002: All channels All alarm OR (2)
H' 00000003: All channels All alarm AND (3)
H' 00000004: All channels Alarm 1 OR (4)
H' 00000005: All channels Alarm 2 OR (5)
H' 00000006: All channels Alarm 3 OR (6)
H' 00000007: All channels Alarm 1 AND (7)
H' 00000008: All channels Alarm 2 AND (8)
H' 00000009: All channels Alarm 3 AND (9)
H' 0000000A: All channels Input error OR (10)
Not used.
H' 00000020: CH1 Alarm 1 (32)
H' 00000021: CH1 Alarm 2 (33)
H' 00000022: CH1 Alarm 3 (34)
H' 00000023: CH1 All alarm OR (35)
H' 00000024: CH1 All alarm AND (36)
H' 00000025: CH1 Input error (37)
Not used.
H' 00000040: Channel 2: The same as channel 1. (64)
···
···
H' 00000800: Channel 64: The same as channel 1.
(2048)
···
0011
Auxiliary Output 2 Assignment
The rest are the same as Auxiliary Output 1 Assignment. 21
0012
Auxiliary Output 3 Assignment
22
0013
Auxiliary Output 4 Assignment
0
···
···
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......