32
DeviceNet Communications Cables Wiring
Section 3-3
Colored stickers that match the colors of the lines to be inserted are provided
on the Master Unit and slaves. Use these stickers to check that the lines are
wired correctly. The colors correspond to the signal lines as follows:
• We recommend the following crimp terminals.
Phoenix Contact AI-series Crimp Terminals: AI-0.5-8WH-B (product code
3201369)
The following crimp tool is also available.
Phoenix Contact ZA3 Crimp Tool
Note
For the DeviceNet power supply, always use an EN/IEC-approved
power supply with reinforced or double insulation.
3-3-2
Attaching the DeviceNet Communications Unit Connector
Align the DeviceNet Communications Unit connector with the cable connector,
and insert the cable connector fully into the DeviceNet Communications Unit
connector.
Tighten the set screws to a torque between 0.25 and 0.30 N·m to secure the
connector.
Color
Signal
Red
Power line, positive voltage (+V)
White
Communications line, high (CAN high)
---
Shield
Blue
Communications line, low (CAN low)
Black
Communications cable, negative voltage (
−
V)
Crimp terminal
Line
Insert the line and crimp.
10
1
NODE
ADR
EJ1N
DRT
COPY
EDS
UP/DN
TC2/4
MODE
NO
MAX
No.
MS
NS
TS
123456
1
0 9
8
7 6
54
3
2
1
0 9
8
7 6
54
3
2
4
5678
9AB
D EF
01
23
C
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...