76
Allocating Data in the Master
Section 4-5
2.
Click the
I/O Information
Tab and click the
Edit
Button. The Change I/O
Size Window will be displayed.
3.
Change the output size and input size for the COS or Cyclic connection to
be used. Set the output size to the same value as the output size of the Poll
connection and set the input size to the size used for allocation area 2 of
on the I/O Allocation (IN) Tab Page for the DeviceNet Communications
Unit.
4.
Select the Unit from the General Tab Page for the master in the Edit Device
Parameters Window of the master, and then click the
Advanced Setup
Button. The Connection Tab Page will be displayed.