111
Sending CompoWay/F Commands to a Temperature Controller
Section 6-2
Command Block
Note
For broadcasting, specify XX (58 hex 58 hex ASCII)
Example: Unit number = 01, FINS-mini command text = 01 01 C0 0000 00
0001 (Executes Read from Variable Area (01 01), to read one element for ch1
PV (C0 0000).)
Response Block
Normal Response
6-2-3
List of FINS-mini Commands
The following table lists the FINS-mini commands that can be sent to the Tem-
perature Controllers. For details on commands and the variable area, refer to
the
EJ1 Temperature Controller User’s Manual
(Cat. No. H142).
Class ID
Instance ID
Data (CompoWay/F command frame data)
0086 hex fixed
0001 hex fixed
1 byte
1 byte
2 bytes
2 bytes
FINS-mini command text
Sub-address
SID
Destina-
tion
node
address
Service
Code
37 hex
fixed
Specified in ASCII code
(See following example.)
Communica-
tions Unit No.
(See note.)
[00]= 3030
hex fixed
[0]= 30
hex
fixed
Communications
Unit No.
Sub-address
SID
FINS-mini command text
30 hex
31 hex
30 hex
30 hex
30 hex
30 hex
31 hex
30 hex
31 hex
43 hex
30 hex
FINS-mini command text
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
31 hex
Data (CompoWay/F response frame data)
Returns in ASCII code
2 bytes
1 byte 1 byte
Communications
Unit No.
Sub-address
End code
FINS-mini response text
No. of receive
bytes
Source
node
address
Service
Code
B7 Hex
fixed
[00]=
3030 Hex
fixed
MRC
SRC
Service name
Description
MRC, SRC notation
CompoWay/F
binary
commands
CompoWay/F ASCII
commands
01
01
Read from Vari-
able Area
Reads a set value.
01 hex 01 hex
30 hex 31 hex 30 hex 31 hex
01
02
Write to Variable
Area
Writes a set value.
01 hex 02 hex
30 hex 31 hex 30 hex 32 hex
01
04
Composite Read
from Variable Area
Reads more than one non-consecu-
tive set value.
01 hex 04 hex
30 hex 31 hex 30 hex 34 hex
01
13
Composite Write
to Variable Area
Writes more than one non-consecu-
tive set value.
01 hex 13 hex
30 hex 31 hex 31 hex 33 hex
01
10
Composite Regis-
tration Read
Reads in order the contents of
addresses specified for composite
read registration of set values.
01 hex 10 hex
30 hex 31 hex 31 hex 30 hex
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...