130
Remote I/O Communications Characteristics
Section 7-1
CS, CJ, C200HX/HG/HE (-Z), and C200HS PLCs
Minimum I/O Response
Time
The minimum I/O response time occurs when the DeviceNet Slave I/O
refreshing is executed just after the input signal is received by the master and
I/O is refreshed for the slave first in the next I/O refresh cycle.
T
IN
:
The Input Slave's ON (OFF) delay (Minimum value: 0)
T
OUT
:
The Output Slave's ON (OFF) delay (Minimum value: 0)
T
RT-IN
:
The Input Slave's communications time/slave
T
RT-OUT
: The Output Slave's communications time/slave
T
PLC
:
The PLC's cycle time
T
RF
:
The PLC's DeviceNet Unit refresh time
Note
Refer to the information on each slave for details on Input and Output Slaves'
ON and OFF delay times. Refer to
7-1-2 CompoWay/F Communications
Cycle Time and Refresh Time
and the Operation Manual for the PLC being
used for details on the PLC's cycle time.
The minimum I/O response time (T
MIN
) is the total of the following terms:
T
MIN
= T
IN
+ T
RT-IN
+ (T
PLC
−
T
RF
) + T
RT-OUT
+ T
OUT
PLC
T
OUT
T
IN
(T
PLC
−
T
RF
)
T
RT-OUT
T
RT-IN
T
RF
T
PLC
Master Unit
Input
Output
Instruction
execution
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...