![background image](http://html1.mh-extra.com/html/omron/ej1-07-2008/ej1-07-2008_operation-manual_743567132.webp)
113
Examples Using CompoWay/F Commands
Section 6-3
Command Details
[CMND S D C]
Response (Operation1)
S
0: 2801 hex
Command code
+1: 0036 hex
DeviceNet Communications Unit node address = 00
Service code = 36 hex
+2: 0086 hex
Class ID = 0086 hex
+3: 0001 hex
Instance ID = 01 hex
+4: 0000 hex
TC2 communications unit number = 00 hex, sub-
address (fixed) = 00 hex
+5: 0001 hex
SID (fixed) = 00 hex MRC = 01 Hex
+6: 02C1 hex
SRC = 02 hex, variable type = 94 hex
+7: 0003 hex
Write start address = 0100 hex (2 bytes)
+8: 0000 hex
Bit position (fixed) = 00 hex, No. of elements = 00
hex (2 bytes)
+9: 0100 hex
No. of elements = 01 hex, Data = 02 hex (4 bytes)
+10: 4000 hex
Data = 04 hex (lower byte (00 hex) is not relevant.)
D
D01200:
First response storage word
C
0: 0015 hex
No. of command data bytes
+1: 000F hex
No. of response data bytes
+2: 0000 hex
Remote (destination) network address = 0
+3: 3FFE hex
Remote (destination) node address = 3F hex
Remote (destination) Unit address = FE hex (10 hex
also possible)
+4: 0000 hex
Response required, communications port No.0, No.
of retries = 0 hex
+5: 0064 hex
Response monitoring time
0: 2801 hex
Command code
+1: 0000 hex
End code (FINS)
+2: 0009 hex
No. of bytes received
+3: 00B6 hex
Node address = 00 hex, Service code = B6 hex
+4: 0000 hex
TC2 communications unit number = 00 hex, Sub-address
(fixed) = 00 hex
+5: 0001 hex
End code (CompoWay/F) = 00 hex, MRC = 01 hex
+6: 0200 hex
SRC = 02 hex, End code (FINS-mini) = 00 hex (2 bytes)
+7: 0000 hex
End code (FINS-mini) = 00 hex (Lower byte (00 hex) is not
relevant.)
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...