88
Operations from the Edit Device Parameters Window
Section 5-2
Setting Method
1,2,3...
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the
General
Tab, and enter the desired value in the
Network
Power Voltage
field.
5-2-5
Setting the Unit Conduction Time Monitor
The DeviceNet Communications Unit can record the conduction time (time
that communications power is supplied to the Unit), and when the value
exceeds the set monitor value, the Unit Maintenance Bit in the Unit Status
Area will be turned ON.
This function provides a guideline for when to replace the Unit.
Measuring unit: 0.1 h (On the Configurator, however, the display unit will
be 1 h.)
Measured time: 0 to 429496729.5 h
(stored data: 00000000 to FFFFFFFF hex)
Monitor value setting range: 0 to 429496729 hours (specify as an integer)
The present value for conduction time and the Unit Status Area can be
checked in the Maintenance Information Window when using Maintenance
Mode.
Note
The present value and monitor value for the conduction time are held even
when the power is turned OFF.
Setting Method
1,2,3...
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the
General
Tab, and enter the desired value in the
Unit Conduc-
tion Time
field.
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...