121
Sending Explicit Messages
Section 6-5
6-5-4
Setting and Monitoring Temperature Controller Channels
Explicit
message
Read
/write
Function
Command
Response
Service
code
Class ID Instance
ID
Attribute
ID
Data size
Tempera-
ture Con-
troller
Channel
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the monitor
mode for maintenance
information of the Tem-
perature Controller unit
number and channel
(see note 1) specified
by the Instance ID (1 to
64).
0E hex
7A hex
01 to 40
hex
65 hex
---
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
Write
Writes the monitor
mode for maintenance
information of the Tem-
perature Controller unit
number and channel
(see note 1) specified
by the Instance ID (1 to
64).
10 hex
7A hex
01 to 40
hex
65 hex
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
---
Set Value
for Unit
Conduction
Time or
Total RUN
Time
Read Reads the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 64).
0E hex
7A hex
01 to 40
hex
68 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Write
Writes the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 64).
10 hex
7A hex
01 to 40
hex
68 hex
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
---
Unit Con-
duction
Time or
Total RUN
Time Read
Read Reads the PV for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 64).
0E hex
7A hex
01 to 40
hex
66 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Monitor
Status of
Unit Con-
duction
Time or
Total RUN
Time Read
Read Reads the monitor sta-
tus for the Unit conduc-
tion time or total RUN
time (unit: s) of the
Temperature Control-
ler unit number and
channel (see note 1)
specified by the
Instance ID (1 to 64).
0E hex
7A hex
01 to 40
hex
67 hex
---
1 byte
00 hex: Within
range
01 hex: Out of
range (monitor
value
exceeded)
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...