Examples Using CompoWay/F Commands
Section 6-3
Program Example (Operation 2)
BSET(07 1)
# 0000
D1 020
MO V(021)
# 2801
D1020
MO V(021)
# 0036
D1021
MO V(021)
# 0086
D1022
D1229
MO V(021)
# 0001
D1023
MO V(021)
# 0000
D1024
MO V(021)
# 0001
D1025
A 20011
MOV(021 )
# 01C0
D1 026
MOV(021 )
# 0000
D1 027
MOV(021 )
# 0000
D1 028
MO V(021)
# 0100
D1029
0 00000
Sets 0000 (clears) in D1020 to D1229.
Sets 2801 in D1020. (Command code = 28 01)
Sets 0086 in D1022. (Class ID = 86)
Sets 0001 in D1023. (Instance ID = 01)
Sets 0001 in D1025. (SID = 00, MRC = 01)
Sets 0000 in D1027. (Read address = 0000)
Sets 0100 in D1029. (Number of elements = 01)
First Scan
Flag ON
Sets 0036 in D1021.
(Slave node address = 00, service code = 36)
Sets 0000 in D1024.
(TC2 communications Unit No. = 00,
sub-address = 00)
Sets 01C0 in D1026.
(SRC = 01, variable type = C0)
Sets 0000 in D1028
(Bit position = 00, No. of elements = 00)
Summary of Contents for EJ1 - 07-2008
Page 3: ...iv...
Page 19: ...xx...
Page 33: ...14 Initial Temperature Controller Settings Section 1 4...
Page 53: ...34 Wiring the Temperature Controllers Section 3 4...
Page 101: ...82 Ladder Programming Examples Section 4 6...
Page 143: ...124 Sending Explicit Messages Section 6 5...
Page 155: ...136 Message Communications Characteristics Section 7 2...
Page 163: ...144 Maintenance Section 8 2...
Page 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Page 197: ...178 Index...