Chapter 3
3-19
Operation
DC Braking Operation
3-6-3 Maximum Output Frequency
• This parameter functions as a frequency limiter.
• Acceleration and deceleration times are defined as the times required to reach the maximum output
frequency (P06) from 0 Hz and to reach 0 Hz from the maximum output frequency (P06).
Note
The setting unit for the frequency reference upper and lower limits is 0.1 Hz for less than
100 Hz, and 1 Hz for 100 Hz or higher.
3-6-4 Setting Frequency Reference Upper and Lower Limits
• Upper and lower limits are set for the frequency reference input from the Digital Operation, fre-
quency references 1 to 4, time-proportional pulse inputs, or communications.
• If the frequency reference lower limit (P08) is higher than the frequency reference upper limit (P07),
operation will be at the frequency lower limit.
• If the frequency reference upper limit (P07) or frequency reference lower limit (P08) is set higher
than the maximum output frequency (P06), the maximum output frequency will be used for the fre-
quency reference upper limit or frequency reference lower limit. (The settings will be automatically
replaced when RUN mode is entered.)
Note
The setting unit for the frequency reference upper and lower limits is 0.1 Hz for less than 100
Hz, and 1 Hz for 100 Hz or greater.
P06
Maximum output frequency
Changes during
operation
No
Setting range
50.0 to 120 (Hz)
Setting unit
0.1 Hz (See note.)
Default setting
60.0
P07
Frequency reference upper limit
Changes during
operation
No
Setting range
0.1 to 120 (Hz)
Setting unit
0.1 Hz (See note.)
Default setting
60.0
Time
(P05)
(P04)
Output frequency
Startup DC injection braking time
DC injection
braking frequency
(P03)
DC injection braking-to-
stop time
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...