Chapter 3
3-17
Operation
3-6
Initial Settings Mode
• It is always possible to change from the RUN mode or adjustment mode to the initial settings mode
by pressing the Mode Key for at least one second while the motor is stopped.
• It is possible to change from the initial settings mode to the RUN mode by pressing the Mode Key
for at least one second while an initial settings mode parameter name (P01 to P21) is displayed.
Display the initial settings mode parameter name by pressing the Enter Key while the set value is
displayed.
• Any set values that are changed will become valid when the RUN mode is entered.
• If the power is turned OFF while a setting has being changed but before RUN mode is entered, the
change will be lost when power is turned back ON.
■
Example Settings in Initial Settings Mode
3-6-1 Setting the Rated Motor Current
• Set P01 to the rated current given on the motor’s nameplate before operation. Setting the rated cur-
rent correctly will protect the motor from burning due to an overload. Read the information in
Motor
Overheating Protection (Electronic Thermal)
under
Precautions for Correct Use
on page 3-2.
Key sequence
Indicator
Display example
Explanation
None
@
Hz set
The entire display and simplified-LED indicators
will light (except for the COM indicator) when
the power supply is turned ON. The present fre-
quency reference will be displayed on the data
display.
1 s min.
None
Pressing the Mode Key for 1 s or longer
changes the mode to the initial settings mode.
p01
will be displayed on the data display.
None
Select the item to be displayed using the Incre-
ment and Decrement Keys.
None
When the Enter Key is pressed, the present set
value for the selected item will be displayed.
None
Use the Increment and Decrement Keys to
make the setting. The data display will flash.
None
Pressing the Enter Key will enter the set value.
When the data displays stops flashing, the
adjustment item name will again appear on the
data display.
1 s min.
@
Hz set
Press the Mode Key for at least 1 s to return to
the RUN mode.
p01
p06
60.0
6.0
p01
p06
60.0
58.3
p06
6.0
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...