Chapter 2
2-34
Design
2-2-6 Harmonics Suppression in General-purpose Inverters
(Input Current of 20 A Maximum)
When equipped with the AC Reactor specified in section 5-2-5, the 3G3JE meets the harmonic sup-
pression guideline for general-purpose inverters (inverters with an input current of 20 A maximum)
issued by the Japan Electronic Device Industrial Council (JEDIC).
2-2-7 Guideline to Reduce Harmonics Emissions in Appliances
Receiving High Voltages or Special High Voltages
The 3G3JE meets the Guideline to Reduce Harmonics Emissions in Appliances Receiving High Volt-
ages or Special High Voltages (JEITA).
■
Guideline Applicability
This guideline is applicable to the following appliances.
1. Appliances receiving power from a 6.6-kV network with a total capacity exceeding 50 kVA consid-
ering the harmonics emission rate for each type of installed device emitting harmonics (called the
equivalent capacity)
2. Appliances receiving power from a 22-kV or 33-kV network with equivalent capacity exceeding
300 kVA
3. Appliances receiving power from a 66-kV or higher network with equivalent capacity exceeding
2,000 kVA
The limit for harmonic current, calculation methods for the equivalent capacity, and calculation meth-
ods for the harmonic current for appliances receiving 6.6 kV are described below.
●
Limit of Harmonic Current
The allowable value for the harmonic current flowing to the network from special appliances is cal-
culated for each harmonic number by multiplying the harmonic current limit per kilowatt of con-
tracted power given in the following table by the contracted power (in kilowatts).
Limits to Harmonic Current per kW of Contracted Power
(Unit: mA/kW)
Received
voltage (kV)
5th
7th
11th
13th
17th
19th
23rd
Higher
than 23rd
6.6
3.5
2.5
1.6
1.3
1.0
0.90
0.76
0.70
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...