Chapter 3
3-18
Operation
• Motor overload (E03) detection is disabled by setting the parameter to 0.0.
Note
The default setting for this parameter is the common rated current of the maximum applicable
motor.
3-6-2 DC Injection Braking Function
The DC injection braking function applies a DC voltage to the induction motor for braking control.
• Startup DC Injection Braking Time
This braking is used for stopping and starting a motor rotating by inertia with no regenerative pro-
cessing.
• DC Injection Braking-to-stop Time
Adjust the stop DC injection braking time if the motor rotating does not decelerate to a stop in nor-
mal operation due to inertia. Increasing the DC injection braking time or DC injection braking fre-
quency reduces the time required to stop the motor.
• When starting, acceleration will start after the startup DC injection braking time (P04) has elapsed.
• After decelerating to the DC injection braking frequency (P03) when stopping, DC injection braking
will be applied for the DC injection braking-to-stop time (P05).
P01
Rated motor current
Changes during
operation
No
Setting range
0.0 to 2.5 (A)
Setting unit
0.1 A
Default setting
See note.
Maximum applicable
motor capacity
Default dated
current setting [A]
0.1 kW
0.6
0.2 kW
1.0
0.4 kW
2.0
P03
DC injection braking frequency
Changes during
operation
No
Setting range
0.0 to 5.0 (Hz)
Setting unit
0.1 Hz
Default setting
3.0
P04
Startup DC injection braking time
Changes during
operation
No
Setting range
0.0 to 10.0 (s)
Setting unit
0.1 s
Default setting
0.0
P05
DC injection braking-to-stop time
Changes during
operation
No
Setting range
0.0 to 10.0 (s)
Setting unit
0.1 s
Default setting
0.5
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...