Chapter 5
5-7
Specifications
■
External Dimensions
5-2-5 AC Reactor
■
3G3IV-PUZBAB
@
(Yaskawa Electric)
Connect an AC Reactor to the Inverter to suppress harmonic current gener-
ated from the Inverter, or if the power supply capacity is much greater than
the Inverter capacity. The AC Reactor also improves the power factor of the
Inverter. Select the AC Reactor model from the following table according to
the motor capacity.
■
Applicable Models
Max.
applicable
motor
capacity (kW)
Model
3G3IV-
PUZBAB
@
Current
(A)
Induc-
tance
(mH)
Loss
(W)
Weight
(kg)
Dimensions (mm)
A
B
C
D
E
F
H
J
K
L
M
0.1 to 0.2
2A7.0MH
2
7.0
8
2.5
120
71
115
40
50
105
20
M6
10.5 7
M4
0.4
2.5A4.2MH 2.5
4.2
15
2.5
120
71
120
40
50
105
20
M6
10.5 7
M4
30 min.
Weight: 3.0 kg
105
50
260
275
150 min.
150 min.
150
(Unit: mm)
Mounting screws: M5
×
3
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...