Chapter 6
6-4
Parameter Tables
Note
The time required to reach the frequency reference from 0 Hz, or to reach 0 Hz from the fre-
quency reference, is as follows:
Acceleration (deceleration) time =
Acceleration (deceleration) time set value
×
Frequency reference value
÷
Maximum output frequency
■
Initial Settings Mode
Display
Name
Description
Setting
range (See
note 1.)
Default
setting
Unit
Refer-
ence
P01
Rated motor current
Used to set the motor's rated current
as the standard current for motor
overload (E03) detection. (Motor
overload protection will be disabled if
0.0 A is set.) The normal rated cur-
rent for a motor with the maximum
capacity supported by the Inverter is
set as the default.
0.0 to 2.5
0.1 kW:
0.6
0.2 kW:
1.0
0.4 kW:
2.0
A
3-17
P02
Accumulated operating
time standard
Used to set the alarm output time for
the accumulated operating time
alarm (E09).
0.0 to 99.9
20.0
Kh
3-23
P03
DC injection braking fre-
quency
Used to set functions for applying DC
current to an inductive motor to brake
the motor. When stopping, DC brak-
ing operates at the DC braking stan-
dard frequency and below.
0.0 to 5.0
3.0
Hz
3-18
P04
Startup DC injection
braking time
0.0 to 10.0
0.0
s
3-18
P05
DC injection braking-to-
stop time
0.0 to 10.0
0.5
s
3-18
P06
Maximum output fre-
quency
Used to limit the frequency. Also used
as a reference frequency for the
acceleration time and deceleration
time.
50.0 to 120
60.0
Hz
3-19
P07
Frequency reference
upper limit
Used to set the upper limit for the fre-
quency reference.
0.1 to 120
60.0
Hz
3-19
P08
Frequency reference
lower limit
Used to set the lower limit for the fre-
quency reference.
0.0 to 120
0.0
Hz
3-19
P09
Momentary power inter-
ruption restart selection
Used to select the processing for
when main-circuit low voltage protec-
tion occurs.
0: Do not continue operation.
1: Continue operation if power inter-
ruption is 0.5 s or less.
2: Always continue operation.
0 (
0
)
1 (
1
)
2 (
2
)
0
None
3-20
P10
Operation command
selection
Used to select the command method
for starting and stopping the Inverter
and the direction of rotation.
Key: Use Digital Operator keys.
PLC: Use the STF and STR control
inputs.
Key (
key
)
PLC (
plc
)
Key
None
3-20
P11
Frequency reference
selection
Used to select the method for input-
ting frequency references.
Key:
Use Digital Operator keys.
MSP: Use frequency references
using multi-step speed refer-
ence 0 (SS0) and multi-step
speed reference 1 (SS1).
T.C:
Time-shared proportional
pulses using multi-step speed
reference 0 (SS0).
Key (
key
)
MSP (
msp
)
T.C (
t.c
)
Key
None
3-21
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...