Chapter 2
2-36
Design
As described below, the result is multiplied by the maximum equipment operating rate to reduce
the current.
The harmonic currents emitted by all devices at the rated operating status are totaled and then
multiplied by the maximum equipment operating rate to calculate the harmonic emission current.
The maximum equipment operating rate is the ratio of the total capacity of the devices emitting
harmonic current to the maximum capacity of the equipment when operating. The maximum ca-
pacity of the equipment when operating is the average value over a 30-minute period.
■
3G3JE Harmonic Current Countermeasures
●
AC Reactors
AC reactors are used to suppress harmonic current. Using an AC reactor will reduce the emission
rate of harmonic current as shown in the following table to improve the power rate on the Inverter’s
input side. The AC reactor functions to suppress sudden currents.
●
Effect of AC Reactor
Harmonic
countermeasure
Harmonic current rate for harmonic numbers (%)
5th
7th
11th
13th
17th
19th
23rd
25th
None
(only Inverter)
65
41
8.5
7.7
4.3
3.1
2.6
1.8
AC Reactor
38
14.5
7.4
3.4
3.2
1.9
1.7
1.3
B1
B2
3G3JE
Inverter
AC Reactor
(optional)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Three-phase
200 to 230 VAC
M
3~
MCCB
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...