Chapter 2
2-11
Design
• For the MCCB's time characteristics, be sure to consider the Inverter's overcurrent protection (one
minute at 150% of the rated output current).
• A sequence that turns OFF the power supply using the alarm (ALM) output of the 3G3JE can be
made as shown in the following diagram.
●
Installing a Ground Fault Interrupter
• Inverter outputs use high-speed switching, so high-frequency leakage current is generated. (In gen-
eral, a leakage current of approximately 100 mA will occur for each Inverter when the power cable
is 1 m and approximately 5 mA for each additional meter of power cable.)
• Use a separate breaker for the power supply input section of the Inverter that removes high-fre-
quency leakage currents and detects only leakage currents with frequencies hazardous to human
beings. Use a breaker with a sensitivity amperage of at least 10 mA per Inverter.
• When using a general leakage breaker, choose a ground fault interrupter with a sensitivity amper-
age of 200 mA or more per Inverter and with an operating time of 0.1 s or more.
●
Installing a Magnetic Contactor
• If the power supply of the main circuit is to be turned OFF because of the sequence, a magnetic
contactor (MC) can be used. (When a magnetic contactor is installed on the primary side of the
main circuit to forcibly stop a load, however, the regenerative braking will not work and the load will
coast to a stop.)
• A load can be started and stopped by switching the magnetic contactor. Frequently switching the
magnetic contactor, however, may cause the Inverter to break down. To maintain the service life of
the Inverter's internal electrolytic capacitors, it is recommended that the MC be switched to start/
stop operation no more than once every 30 minutes.
• When the Inverter is operated with the Digital Operator, automatic operation cannot be performed
after recovery from a power interruption.
●
Connecting Input Power Supply to the Terminal Block
Input power supply can be connected to any terminal on the terminal block because the phase
sequence of input power supply is irrelevant to the phase sequence (R/L1, S/L2, and T/L3).
R/L1
S/L2
T/L3
X1
X2
ON
OFF
3G3JE
Inverter
ALM (+)
ALM (
−
)
Three-phase
200 to 230 V AC
X1
X1
X2
MCCB
(30 VDC, 50 mA max.)
DC (24 V) relay
Summary of Contents for EasySpeed 3G3JE
Page 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Page 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Page 18: ...Table of Contents XVI...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Page 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Page 86: ...Chapter 3 3 26 Operation...
Page 100: ...Chapter 4 4 14 Maintenance Operations...
Page 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Page 112: ...Chapter 5 5 12 Specifications...
Page 113: ...Chapter 6 Parameter Tables...
Page 118: ...Chapter 6 6 6 Parameter Tables...
Page 130: ...Chapter 7 7 12 Appendix...
Page 132: ...R 2 Revision History...