265
3-3-1 Control Modes
Control is performed independently for each control loop based on the set point
data. The relationship between the set point data and the control operation is
shown in the following table.
Set point
Control operation
F999 to 9999
Normal temperature control performed.
CCCC
Control stopped.
Other settings
Temperature control performed according to the most recent valid
set point data. The PV will be EE01.
If the temperature exceeds the range from –999 to 9999, the process value data
in the Temperature Controller will be frozen at –999 or 9999 and the data will be
maintained at F999 or 9999, respectively.
The process value data will be set to FFFF during initialization; do not read the
data as the process value at this time.
Short-circuit Protection
If the output is shorted, short-circuit protection will operate, turning the output
OFF. To reset the short-circuit protection, either turn off the power supply or set
the set point data to CCCC to stop control operation.
3-3-2 Switch Settings
1, 2, 3...
1. Set the function DIP switch pins (SW1) before connecting the Temperature
Control Unit to the other Units of the PC.
2. All pins on the DIP switch are factory-set to OFF.
3. Use a pen tip or other pointed object to set the pins of the DIP switch.
Pin
Function
OFF
ON
1
Control mode
ON/OFF
Advanced PID
2
Control operation
Reverse (heating
control)
Normal (cooling control)
3
Temperature scale
°
C
°
F
4
Input sensor
TC00
j
: K
TC10
j
: JPt100
TC00
j
: J
TC10
j
: Pt100
5
Number of control loops
(control points)
Two loops
One loop
6
Control period
20 s
2 s
Control Operation
Reverse Control
Used for heating control with heaters. If the temperature is lower than the set
temperature (i.e., the temperature has negative deviation), the output of the
heaters will be increased.
Normal Control
Used for suppressing excessively high temperature with cooling water. If the
temperature is higher than the set temperature (i.e., the temperature has posi-
tive deviation), the output of the cooling water will be increased.
Nomenclature
Section 3-3
Summary of Contents for CQM1H - 08-2005
Page 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Page 2: ......
Page 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Page 4: ......
Page 6: ......
Page 12: ......
Page 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Page 22: ......
Page 42: ......
Page 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Page 46: ......
Page 62: ......
Page 72: ......
Page 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Page 78: ......
Page 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Page 80: ......
Page 88: ......
Page 92: ......
Page 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Page 94: ......
Page 118: ......
Page 120: ......
Page 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Page 122: ......
Page 126: ......
Page 140: ......
Page 142: ......
Page 144: ......
Page 156: ......
Page 172: ......
Page 186: ......
Page 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Page 188: ......
Page 192: ......
Page 204: ......
Page 218: ......
Page 238: ......
Page 242: ......
Page 246: ......
Page 248: ......
Page 250: ......