The nonvolatile memory can store the zero shift value.
While the forced-zero state stays in effect, the ZERO indicator is lit.
Note The forced zero function is not effective when the timing hold mode is set to
peak-to-peak hold.
2-6
Voltage Monitor Output
The CQM1-LSE02 has a voltage monitor output function.
Scaled conversion data monitor mode or set data D/A output mode can be se-
lected.
The Unit refreshes its monitor output at 0.5-s intervals.
In this mode, it is possible to output voltage corresponding to the scaled conver-
sion data.
Example of Scaling into the Data between 0000 to 5000 for the Input be-
tween 4 to 20 mA
When the input is 12 mA, the scaled conversion data becomes 2500 and the out-
put voltage that corresponds to this value becomes 2.5 V.
Scaled conversion data
Input value (mA)
0
4
12
20
2500
5000
–9999
–9.999
2500
9999
9.999
2.5
Output voltage (V)
Scaled con-
version data
(decimal)
In this mode, the monitor output terminal of the CQM1-LSE02 will have voltage
output corresponding to the signed binary data stored in the output word of the
CQM1-LSE02 by easy use of the ladder program.
The signed binary data range of the CQM1-LSE02 is from –9999 (D8F1) to 9999
(270F) and the voltage output range of the CQM1-LSE02 corresponding to the
signed binary data range is from –9.999 to 9.999 V.
If the signed binary data out of the range is stored in the output word, either
–9.999 or 9.999 V will be output. For example, if the signed binary data D8F0
(–10000 in BCD) is written, the voltage of the monitor output will be –9.999 V.
Note In case of using the Unit in the set data D/A output mode, when obtaining the
value to be set to the output word through calculation using the ladder program,
etc., be careful not to use the computed result of “C000 to CFFF.” Even when the
Unit is used in the set data D/A output mode, if “C000 to CFFF” is set to the output
word, it is treated as a command.
In this mode, analog input is converted into digital data and then converted into
analog output. Therefore, the obtained analog output is not highly precise.
Scaled Conversion Data
Monitor Mode
Set Data D/A Output Mode
Voltage Monitor Output
Section 2-6
Summary of Contents for CQM1H - 08-2005
Page 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Page 2: ......
Page 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Page 4: ......
Page 6: ......
Page 12: ......
Page 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Page 22: ......
Page 42: ......
Page 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Page 46: ......
Page 62: ......
Page 72: ......
Page 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Page 78: ......
Page 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Page 80: ......
Page 88: ......
Page 92: ......
Page 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Page 94: ......
Page 118: ......
Page 120: ......
Page 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Page 122: ......
Page 126: ......
Page 140: ......
Page 142: ......
Page 144: ......
Page 156: ......
Page 172: ......
Page 186: ......
Page 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Page 188: ......
Page 192: ......
Page 204: ......
Page 218: ......
Page 238: ......
Page 242: ......
Page 246: ......
Page 248: ......
Page 250: ......