!
84
If input data is below the converted range (i.e., the input voltage of the data is
less than approximately 0.95 V or the input current of the data is less than
approximately 3.8 mA), the broken wire detection function of the Analog Input
Unit will be activated.
0
Input voltage (current)
1 V (4 mA)
3 V (12 mA)
5 V (20 mA)
Conversion data
* “H” indicates hexadecimal.
(4048) 0FD0H*
(4095) 0FFFH*
(2048) 0800H*
(0048) 0030H*
(0000) 0000H*
Approx. 5.4 V
Approx. 0.95 V
Caution
The Analog Input Unit converts inputs 1, 2, 3, 4, 1, etc., in this order. If the input
range is 1 to 5 V or 4 to 20 mA, the Analog Input Unit may be influenced by the
previous input if the input has changed greatly. Avoid setting a range of –10 to 10
V as much as possible before using an input range of 1 to 5 V or 4 to 20 mA.
The mean value processing function of the Analog Input Unit is activated by set-
ting pin 10 of the Analog Input Unit’s DIP switch to ON. If the mean value proces-
sing function is activated, all input values (inputs 1 to 4) will be averaged.
The mean value processing function enables the Analog Input Unit to convert
each input value eight times, average the values, and store the results as digital
conversion data in the input word. The contents of the word are refreshed with
intervals of approximately 72 ms.
Note By using the AVG instruction of the CPU, only particular input values can be av-
eraged or the number of averaging operations can be changed.
Broken Wire Detecting Function
•
The broken wire detecting function of the Analog Input Unit makes it possible to
detect and alarm the disconnection of any wire that has been connected to the
Analog Input Unit.
•
The broken wire detecting function of the Analog Input Unit will work when the
input voltage and current drops to approximately 0.95 V and 3.8 mA or lower if
the Analog Input Unit is set to a range of 1 to 5 V or 4 to 20 mA.
•
When the Analog Input Unit detects wire disconnection, the broken wire de-
tecting indicator (BROKEN WIRE) will be lit and the broken wire flag of the in-
put that has been disconnected will be set to 1. (Refer to 3-3-2 Adjustment)
•
The broken wire detecting indicator will reset to OFF automatically when the
input returns to normal.
Mean Value Processing
Function
Functions
Section 2-2
Summary of Contents for CQM1H - 08-2005
Page 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Page 2: ......
Page 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Page 4: ......
Page 6: ......
Page 12: ......
Page 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Page 22: ......
Page 42: ......
Page 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Page 46: ......
Page 62: ......
Page 72: ......
Page 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Page 78: ......
Page 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Page 80: ......
Page 88: ......
Page 92: ......
Page 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Page 94: ......
Page 118: ......
Page 120: ......
Page 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Page 122: ......
Page 126: ......
Page 140: ......
Page 142: ......
Page 144: ......
Page 156: ......
Page 172: ......
Page 186: ......
Page 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Page 188: ......
Page 192: ......
Page 204: ......
Page 218: ......
Page 238: ......
Page 242: ......
Page 246: ......
Page 248: ......
Page 250: ......