Potentiometers P1 and P2 and diagnostic LEDs
The enable signal (Start/Stop) is implemented with the external switch. The setpoint value can be fixed with
the integrated potentiometer P1. The potentiometer P2 is available for selection of the start-up and braking
ramps.
SK
200E,
top
view
RJ12
RS
232
RS
485
P1
/
P2
LED
‐
FI
LED
‐
ASi
Diagnostic
LEDs
Diagnostic LEDs (4.1.2.1)
Potentiometer and LEDs (4.1.2.2)
P1
(continuous)
P2
(stepped)
1 yellow
Digital
output
0% P102/103 P105 -
-
-
2
yellow
Digital input 1
10% 0.2s
10Hz
1
P102/103 P104
3
yellow
Digital input 2
20% 0.3s
20Hz
2 0.2s 2Hz
4
yellow
Digital input 3
30% 0.5s
30Hz
3 0.3s 5Hz
5
yellow
Digital input 4
40% 0.7s
40Hz
4 0.5s 10Hz
6 yellow
Motor
PTC
50% 1.0s
50Hz
5 0.7s 15Hz
7
yellow
Brake chopper active
60% 2.0s
60Hz
6 1.0s 20Hz
8
yellow
Mech. brake status
70% 3.0s
70Hz
7 2.0s 25Hz
9
green
Bus Status 1
80% 5.0s
80Hz
8 3.0s 30Hz
10
red
Bus Status 2
90% 7.0s
90Hz
9 5.0s 35Hz
100% 10.0s
100Hz
10 7.0s 40Hz
The function of P1 and P2 depends on DIP 4/5 (Section 4.1.1).
The function changes according to the setting.
As standard, P1 sets the setpoint value of 0-100% and P2 sets the
ramp from 0.2-7sec.
LED
FI
green
red
Ready / Load (flashing)
Error / Error number (flashing)
LED
AS-I
green
red
AS-Interface status (dual LED)